An assessment of ageing of oxide varistors exposed to pulse hazards using dielectric spectroscopy

Jaroszewski, M (Wroclaw University of Technology, Poland) ; Pospieszna, J (Wroclaw University of Technology, Poland)

2004-04-05

Abstract: The common use of zinc oxide varistors has brought about qualitative changes in the overvoltage protection of electronic and electric power equipment. This is due to the special properties of ZnO varistors, mainly the high current-voltage characteristic nonlinearity and the capacity to withstand strong current surges. In service conditions varistors are exposed to the sustained action of constant or variable voltage or momentary overvoltage pulses. As a result varistors may undergo degradation reflected in changes in their current-voltage characteristics. The changes are manifested in an increase in leakage current and are limited to a highly thermally activated low-current region where the performance of the varistor is determined by the parameters of the potential barriers. Thus one can conclude that the degradation is a result of processes leading to the movement of ions and the deformation of the potential barriers. Therefore dielectric spectroscopy (testing of the dielectric response in a wide frequency band) could be useful for the investigation of degradation changes, and so this method is proposed in this paper.

Keyword(s): dielectric spectroscopy ; overvoltage pulse ; oxide varistor
Note: Proceedings of the 2004 IEEE International Conference on Solid Dielectrics. ICSD 2004, Toulouse, France, July 5-9, 2004. Vol. 2. Piscataway, NJ : IEEE Service Center, 2004. pp. 727-730


Fulltext : http://zet10.ipee.pwr.wroc.pl/record/144/files/

Cited by: try citation search for ENY-ARTICLE-2008-115; I07/2004/I-019

Rekord stworzony 2008-03-23, ostatnia modyfikacja 2008-03-24

Podobne rekordy


 
Osoby, które oglądały tę stronę, oglądały również:
(899)  Proceedings of the Int. Conference "7th EEEIC International Workshop on Environment and Electrical Engineering" - Schwarz, H et al - ENY-PREPRINT-2008-008
(895)  Impact of Distributed Generation on Electrical Power Network - Khan, U N - ENY-ARTICLE-2008-142
(887)  Evaluation of compensation devices of DC arc furnaces using advanced spectrum estimation methods - Bracale, A et al - ENY-ARTICLE-2008-011
(881)  Adaptacyjne sieci neuronowe w zastosowaniu do identyfikacji stanu układów elektrycznych - Kostyla, P - ENY-THESIS-2008-005
(868)  Parametric methods for time-frequency analysis of electric signals - Leonowicz, Z - ENY-BOOK-2008-001

 
Oceń ten dokument:
Bądź pierwszy i oceń ten dokument.


Dyskusja nad tym dokumentem:
Rozpocznij dyskusję o tym dokumencie.