Published Article
/ | ENY-ARTICLE-2008-127 |
Ultrasonic Non-Destructive Diagnostics of HV Insulators
Ranachowski, P (Institute of Fundamental Technological Research PAS) ; Rejmund, F (Wroclaw University of Technology)
2008-04-06
Abstract: The paper presents non-destructive ultrasonic method for investigations of long-rod insulators, operated on overhead power lines and stations. It was established correlation between the degree of C 120 porcelain material degradation and the parameters of ultrasonic wave propagation and attenuation. As example of application of the method there were presented ultrasonic examinations of two groups of insulators – 15 line and 49 station post. On the basis of the measurements advancement of ageing degradation of the material and the quality of the tested insulators were ascertained.
Keyword(s): EEEIC ; ultrasonic method ; non-destructive method ; insulator
Note: Proceedings of the 7th Int. Conference EEEIC 2008, Cottbus, 5-11.05.2008, pp. 14-17
Fulltext : http://zet10.ipee.pwr.wroc.pl/record/165/files/
Cited by: try citation search for ENY-ARTICLE-2008-127
Record created 2008-04-22, last modified 2008-05-31
Similar records
People who viewed this page also viewed: |
|
|
Be the first to review this document.
Start a discussion about any aspect of this document.