000000210 100__ $$aRebizant, W$$uInstitute of Electrical Power Engineering, Wroclaw University of Technology, Poland
000000210 245__ $$aFuzzy Logic Application to Out-Of-Step Protection of Generators
000000210 260__ $$c2001-01-24
000000210 300__ $$a6p
000000210 500__ $$a2001 IEEE Power Engineering Society Summer Meeting, Vancouver, Canada 15-19 July 2001. Piscataway, NJ : IEEE, 2001.
000000210 520__ $$aEfficient protection scheme against out-of-step (OS) conditions based on fuzzy logic (FL) technique is presented. The protection proposed makes use of an adaptive-network-based fuzzy inference system (ANFIS). The FL-based OS protection scheme developed has been thoroughly optimized and tested with ATP-generated case signals. The scheme designed displays almost perfect efficiency and high speed of OS detection. With the scheme designed the OS cases are identified much earlier comparing to standard impedance-based protection schemes. Wide robustness features of the ANFIS-based scheme have also been achieved.
000000210 6531_ $$asynchronous machines
000000210 6531_ $$asynchronous generator stability
000000210 6531_ $$aprotective relaying
000000210 6531_ $$aartificial intelligence
000000210 6531_ $$afuzzy logic
000000210 6531_ $$ainference mechanisms
000000210 6531_ $$atransient analysis
000000210 6531_ $$asimulation