Published Article
/ | ENY-ARTICLE-2008-180 |
Effect of Voltage Harmonics Content on Arrester Diagnostic Result
Jaroszewski, M (Wrocław University of Technology) ; Kostyla, P (Wrocław University of Technology) ; Wieczorek, K (Wrocław University of Technology)
2008-09-30
Abstract: Diagnoses of HV arresters are usually based on an analysis of total leakage current harmonics. The fact that the harmonics content in the supply voltage can be a source of errors is seldom taken into account when routine diagnostic measurements are made. In this paper the effect of harmonics in the voltage signal on the diagnostic result is analysed using Matlab computer simulations.
Keyword(s): arrester ; varistor ; ZnO ; harmonics ; diagnostic
Note: 2004 International Conference on Solid Dielectrics, Toulouse, France, July 5-9, 2004
Fulltext : http://zet10.ipee.pwr.wroc.pl/record/230/files/
Cited by: try citation search for ENY-ARTICLE-2008-180
Record created 2008-09-30, last modified 2008-09-30