Format: HTML | BibTeX | DC | EndNote | NLM | MARC | MARCXML
Published Article / I07/2007/I-043 ENY-ARTICLE-2008-187

Termovision diagnostics of metal oxide surge arresters

Chrzan, K L (Wroclaw University of Technology)

2007-02-05

Abstract: The surge arresters diagnostics based on infrared temperature measurement was evaluated. The 110 kV metal oxide arresters with porcelain housings with two different varistor columns were used. The first one consisted of new varistor elements and the second one consisted of in field degraded varistors. The internal temperature was measured by means of two Tinytalk probes inserted in the varistor column at the bottom and at the top. The external temperature of the housing was measured by means of infrared camera. The maximum temperature of new varistors has grown about VC over the ambient temperature and the external temperature of the housing increased about 1°C only. The temperature of deteriorated varistors increased up to 15°C. Therefore, the arrester housing temperature increased about VC.

Keyword(s): diagnostics ; surge arrester ; termovision
Note: 15th International Symposium on High Voltage Engineering. ISH. Proceedings , Ljubljana, Slovenia, August 27th-31st, 2007 / Eds Maks Babuder, Janko Kosmac, Mladen Iglic. Ljubljana : Faculty of Electrical Engineering University of Ljubljana, Elektroinstitut Milan Vidmar, 2007


Fulltext : http://zet10.ipee.pwr.wroc.pl/record/238/files/

Cited by: try citation search for ENY-ARTICLE-2008-187; I07/2007/I-043

Record created 2008-10-10, last modified 2008-10-10

Ähnliche Datensätze


 
Benutzer, die diese Seite angeschaut haben, haben auch angeschaut:
(1148)  Proceedings of the Int. Conference "7th EEEIC International Workshop on Environment and Electrical Engineering" - Schwarz, H et al - ENY-PREPRINT-2008-008
(1128)  Impact of Distributed Generation on Electrical Power Network - Khan, U N - ENY-ARTICLE-2008-142
(1119)  Adaptacyjne sieci neuronowe w zastosowaniu do identyfikacji stanu układów elektrycznych - Kostyla, P - ENY-THESIS-2008-005
(1101)  Evaluation of compensation devices of DC arc furnaces using advanced spectrum estimation methods - Bracale, A et al - ENY-ARTICLE-2008-011
(1093)  Parametric methods for time-frequency analysis of electric signals - Leonowicz, Z - ENY-BOOK-2008-001

 