Format: HTML | BibTeX | DC | EndNote | NLM | MARC | MARCXML
Published Article / I07/2000/I-059 ENY-ARTICLE-2008-193

Diagnostics of high voltage metal oxide arresters procedure errors

Chrzan, K L (Wroclaw University of Technology, Poland) ; Koehler, W (University of Stuttgart, Germany)

1999-04-03

Abstract: A technique has been described which can determine ac resistive current directly or by obtaining the watt loss of the test specimen and dividing by the true rms (trms) value or the applied voltage. The procedure errors with standard voltage dividers and digital systems have been calculated. Special attention was paid to the voltage shift. A new method for the direct resistive current measurement was proposed. The effect of small amount of harmonics was shown.

Keyword(s): phase shift ; diagnostics ; surge arrester
Note: Eleventh International Symposium on High-Voltage Engineering. ISH 99, [London, 22-27 August 1999]. Vol. 2 London : IEE, cop. 1999. s. 2., 385


Fulltext : http://zet10.ipee.pwr.wroc.pl/record/247/files/

Cited by: try citation search for ENY-ARTICLE-2008-193; I07/2000/I-059

Record created 2008-10-29, last modified 2008-10-30

Similar records


 
People who viewed this page also viewed:
(879)  Proceedings of the Int. Conference "7th EEEIC International Workshop on Environment and Electrical Engineering" - Schwarz, H et al - ENY-PREPRINT-2008-008
(866)  Adaptacyjne sieci neuronowe w zastosowaniu do identyfikacji stanu układów elektrycznych - Kostyla, P - ENY-THESIS-2008-005
(859)  Impact of Distributed Generation on Electrical Power Network - Khan, U N - ENY-ARTICLE-2008-142
(850)  Measurement of IEC Groups and Subgroups Using Advanced Spectrum Estimation Methods - Bracale, A et al - ENY-ARTICLE-2008-117
(846)  Evaluation of compensation devices of DC arc furnaces using advanced spectrum estimation methods - Bracale, A et al - ENY-ARTICLE-2008-011

 
Rate this document:
Be the first to review this document.


Discuss this document:
Start a discussion about any aspect of this document.