Format: HTML | BibTeX | DC | EndNote | NLM | MARC | MARCXML
Published Article / ENY-ARTICLE-2008-201

New Criteria of Voltage Stability Margin for the Purpose of Load Shedding

Wiszniewski, A (Institute of Power System Engineering, Wroclaw University of Technology, Wroclaw, Poland )

2006-02-23

Abstract: Voltage instability is a phenomenon which often contributes to the development of power system disturbances. While increasing load admittance, bus voltage decreases to such a degree that the apparent power (V^2 Y) does not increase. As a result, voltage collapses with all consequences resulting from it. During the large-scale power system disturbance, the last line of defense is the load shedding at the stations, where the stability margin becomes dangerously low. To do that, there is a need to use automatic devices which process local signals, detect the decreased margin, and activate the load shedding. As a criteria of operating such devices, the voltage level is adopted. The disadvantage of such an approach results from the fact that the relations between the voltage level and the stability limit depend very much on the load power factor. To overcome this weakness, this paper presents a criterion which is directly based on the definition of voltage stability. It calculates the derivative of apparent power against the admittance (dS/dY). It may be easily accomplished, because both the power and the admittance are measurable, and the changes of load occurs continuously, as a result of switching on and off the impedances, and/or actions of the transformer on load tap-changing devices.

Keyword(s): disturbances ; load shedding ; power systems ; voltage collapse ; voltage stability
Note: IEEE Transactions on Power Delivery, Vol. 22, No. 3, July 2007, pp. 1367-1371


Fulltext : http://zet10.ipee.pwr.wroc.pl/record/255/files/

Cited by: try citation search for ENY-ARTICLE-2008-201

Rekord stworzony 2008-11-08, ostatnia modyfikacja 2008-11-08

Podobne rekordy


 
Osoby, które oglądały tę stronę, oglądały również:
(812)  Proceedings of the Int. Conference "7th EEEIC International Workshop on Environment and Electrical Engineering" - Schwarz, H et al - ENY-PREPRINT-2008-008
(798)  Adaptacyjne sieci neuronowe w zastosowaniu do identyfikacji stanu układów elektrycznych - Kostyla, P - ENY-THESIS-2008-005
(788)  Impact of Distributed Generation on Electrical Power Network - Khan, U N - ENY-ARTICLE-2008-142
(776)  Evaluation of compensation devices of DC arc furnaces using advanced spectrum estimation methods - Bracale, A et al - ENY-ARTICLE-2008-011
(774)  Measurement of IEC Groups and Subgroups Using Advanced Spectrum Estimation Methods - Bracale, A et al - ENY-ARTICLE-2008-117

 
Oceń ten dokument:
Bądź pierwszy i oceń ten dokument.


Dyskusja nad tym dokumentem:
Rozpocznij dyskusję o tym dokumencie.