000000265 245__ $$aInefficacy of radioactive terminals and early streamer emission terminals
000000265 260__ $$c2003-07-24
000000265 300__ $$a4p
000000265 500__ $$aProceedings of the XIIIth International Symposium on High Voltage Engineering. XIII ISH , Delft, [the] Netherlands, August 25-29, 2003, 4 p.
000000265 520__ $$aThe paper reviews about research of radioactive lightning rods carried out 30 years ago and about new measurements of early streamer emission terminals. Lightning damage on over 100 buildings equipped with ESE terminals in Malaysia and on one family house in Poland is reported. The main measure criterion was the breakdown voltage of the air gap consisted of the high voltage electrode (rod or plate) and a grounded radioactive or ESE terminal. These careful measurements show that the air gaps with ESE terminals have the same breakdown voltages as the air gaps with standard rods. Therefore the big protection zone of ESE terminals as claimed by their manufactures seem to be impossible.