Abstract: The evaluation of electrical stress of polluted outdoor insulators was carried out at the field test station located at a copper smelting plant Głogów in 1987 and 2002. Leakage current and flashover voltages were recorded on porcelain long rods of different types. A simple impulse counters having three different trigger levels were used for current measurements. The special fuses with an explosion mixture were applied for detection of flashovers. Additionally, the measurements of ESDD on insulator surface or dust deposition density were carried out. During last ten years the industry dust emission in Middle Europe decreased considerably due to progress in environmental protection. Therefore the similar measurements were repeated with the aim to asses the current state of electrical stress of outdoor insulators.

Keyword(s): insulators ; electrical stress ; dust emission
Note: XIII International Symposium on High Voltage Engineering, The Netherlands, 2003, (C) Millpress, Rotterdam.


Fulltext : http://zet10.ipee.pwr.wroc.pl/record/269/files/

Cited by: try citation search for ENY-ARTICLE-2008-215

Rekord stworzony 2008-11-26, ostatnia modyfikacja 2008-11-28

Podobne rekordy


 
Osoby, które oglądały tę stronę, oglądały również:
(911)  Impact of Distributed Generation on Electrical Power Network - Khan, U N - ENY-ARTICLE-2008-142
(900)  Measurement of IEC Groups and Subgroups Using Advanced Spectrum Estimation Methods - Bracale, A et al - ENY-ARTICLE-2008-117
(895)  Evaluation of compensation devices of DC arc furnaces using advanced spectrum estimation methods - Bracale, A et al - ENY-ARTICLE-2008-011
(891)  Zadania 1 Podstawy Elektrotechniki Automatyka i Robotyka - Hejke, I et al - ENY-TEACHING-2008-020
(889)  Adaptacyjne sieci neuronowe w zastosowaniu do identyfikacji stanu układów elektrycznych - Kostyla, P - ENY-THESIS-2008-005

 
Oceń ten dokument:
Bądź pierwszy i oceń ten dokument.


Dyskusja nad tym dokumentem:
Rozpocznij dyskusję o tym dokumencie.