Format: HTML | BibTeX | DC | EndNote | NLM | MARC | MARCXML
Published Article / ENY-ARTICLE-2008-220

Performance of Hydrophobic Epoxy Insulators under Industrial Pollution

Chrzan, K L (Wroclaw University of Technology, Poland)

2007-08-01

Abstract: Cycloaliphatic epoxy resins have been used alongside silicones and ceramics for more than 30 years as insulation materials for outdoor applications. Insulators made of cycloaliphatic epoxies offer many advantages overer those made of ceramic or silicones. Standard cycloaliphatic epoxies are construction materials, however, they do not exhibit hydrophobicity as do silicones. A new generation of cycloaliphatic epoxy systems with enhanced hydrophobic properties, hydrophobic cycloaliphatic epoxy try to join the advantages of both cycloaliphatic epoxy resins and silicones The paper presents the laboratory and field test results of comercially available hydrophobic cycloaliphatic epoxy insulators. These insulators exhibit the hydrophobic properties under clean conditions. Unfortunately, when polluted by industrial dust the surface becomes hydrophilic. No hydrophobicity transfer was round even three months after surface contamination. Nevertheless, compared with the standard cycloaliphatic epoxy the hydrophobic cycloaliphatic epoxy offers some advantage under light industrial pollution or sea pollution.

Keyword(s): pollution ; insulators ; surface properties ; epoxy resin
Note: XVth International Symposium on High Voltage Engineering University of Ljubljana, Elektroinštitut Milan Vidmar, Ljubljana, Slovenia, August 27-31, 2007, paper No. T4-86


Fulltext : http://zet10.ipee.pwr.wroc.pl/record/275/files/

Cited by: try citation search for ENY-ARTICLE-2008-220

Record created 2008-12-11, last modified 2008-12-12

Similar records


 
People who viewed this page also viewed:
(1131)  Impact of Distributed Generation on Electrical Power Network - Khan, U N - ENY-ARTICLE-2008-142
(1098)  Zadania 1 Podstawy Elektrotechniki Automatyka i Robotyka - Hejke, I et al - ENY-TEACHING-2008-020
(1093)  Adaptacyjne sieci neuronowe w zastosowaniu do identyfikacji stanu układów elektrycznych - Kostyla, P - ENY-THESIS-2008-005
(1072)  Proceedings of the Int. Conference "7th EEEIC International Workshop on Environment and Electrical Engineering" - Schwarz, H et al - ENY-PREPRINT-2008-008
(1071)  Measurement of IEC Groups and Subgroups Using Advanced Spectrum Estimation Methods - Bracale, A et al - ENY-ARTICLE-2008-117

 
Rate this document:
Be the first to review this document.


Discuss this document:
Start a discussion about any aspect of this document.