000000276 245__ $$aPerformance of Composite Insulators Without Sheds under Light Pollution
000000276 260__ $$c2007-08-01
000000276 300__ $$a4p
000000276 500__ $$aXVt h International Symposium on High Voltage Engineering University of Ljubljana, Elektroinštitut Milan Vidmar, Ljubljana, Slovenia, August 27-31, 2007, paper No. T4-124.
000000276 520__ $$aThe test of insulators without sheds or with small sheds number at Glogow pollution station was described. The performance of insulators with different leakage distance and position (horizontal or vertical) under light pollution is studied. The flashovers, leakage currents and surface erosion were monitored. The 75 kV test voltage is 4 kV higher than the maximum phase to ground voltage of 110 kV system. After long term testing the leakage distance of 80 cm was as withstand distance for horizontal rods and 100 cm for vertical rods. For practical proposes the security factor of 1.3 should be taken into account. Finally, under light pollution the 110 kV composite insulator, in horizontal position could be installed in the form of 100 cm long rods without sheds and vertical insulators with terminal distance of 100 em should have at least two additional sheds.
000000276 6531_ $$apollution