Format: HTML | BibTeX | DC | EndNote | NLM | MARC | MARCXML
000000293 001__ 293
000000293 037__ $$aENY-ARTICLE-2009-234
000000293 041__ $$aeng
000000293 100__ $$aChrzan, K L$$uWroclaw University of Technology, Poland
000000293 245__ $$aInternal Arcing Test on Polluted High Voltage Surge Arresters
000000293 260__ $$c1994-12-29
000000293 300__ $$a4p
000000293 500__ $$aNinth International Symposium on High Voltage Engineering, Graz, Austria, Aug-Sep, 1995, pp. 3220-1 - 3220-4.
000000293 520__ $$aA test to prove the performance of extremely non-uniform polluted single unit metal oxide (MO) and gapped arresters (SiCA) is presented. The test procedure used represents the worst case condition which can occur especially under a small wetting rate and at severe polluted arrester housings. The resulting temperature increase of metal or silicon carbide varistors was measured. Internal partial discharges or internal arcing during the test were also investigated. Currents, power dissipation, voltage distribution along varistors and pollution layer and lightning sparkover voltage were measured or have been calculated.
000000293 6531_ $$ametal oxide arrester
000000293 6531_ $$agapped arrester
000000293 6531_ $$apollution
000000293 6531_ $$apartial discharge
000000293 700__ $$aKohler, W$$uUniversity of Stuttgart, Germany
000000293 700__ $$aFeser, K$$uUniversity of Stuttgart, Germany
000000293 8560_ $$fleon99@pwr.wroc.pl
000000293 8564_ $$uhttp://zet10.ipee.pwr.wroc.pl/record/293/files/$$zAccess to Fulltext
000000293 909CO $$ooai:zet10.pwr.wroc.pl:293$$pglobal
000000293 980__ $$aARTICLE