Published Article
/ | ENY-ARTICLE-2009-265 |
Assessment of transient disturbances in HV systems with single-phase autoreclosures
Lobos, T (Wroclaw University of Technology, Poland) ; Schegner, P (Technical University of Dresden, Germany) ; Sikorski, T (Wroclaw University of Technology, Poland)
2009-05-12
Abstract: This paper proposes some extended method for assessment of transient disturbances in HV system with single-phase autoreclosures. Main efforts are addressed to second arc extinction on the basis of recorded voltage in faulty line in presence of arc. Introduced ideas utilizes recent definitions of time-varying power quality indices. A new contribution of the work is a proposition of characteristic based on local values of odd and even harmonics distortion index.
Keyword(s): transient disturbances ; autoreclosure ; HV ; distortion index
Note: XV International Symposium on Theoretical Electrical Engineering, ISTET 2009, Lubeck, Germany, 20-24 June 2009,