Published Article
/ | ENY-ARTICLE-2012-310 |
OUTDOOR INSULATORS AND HOUSINGS BREAKDOWNS CAUSED BY POLLUTION
Chrzan, K L (Wroclaw University of Technology) ; Znaidi, R (Dar Abou Zakaria, Kélibia la Blanche 8090 Kélibia)
2012-04-17
Abstract: A heavy pollution on outdoor insulators causes electrical discharges, flashovers, surface erosion or tracking. In extremely cases the dielectric breakdowns occur. In this paper the breakdowns of four insulators has been shown: porcelain bushing insulators on rectifier set ups of electrostatic precipitators, the porcelain fuse cutouts, a porcelain housing of metal oxide surge arrester and polymer concrete insulators. The analysis of other damages of condenser bushings and instrument transformers published in the literature has led us to a hypothesis that a part of these failures could be initiated or accelerated by external pollution.
Keyword(s): Surface erosion ; porcelain bushing ; polymer concerete insulators
Note: XVII International Symposium on High Voltage Engineering, Hannover, August 22-26, 2011, paper E-001
Fulltext : http://zet10.ipee.pwr.wroc.pl/record/397/files/
Cited by: try citation search for ENY-ARTICLE-2012-310
Record created 2012-04-17, last modified 2012-04-18
Similar records
People who viewed this page also viewed: |
|
|
Be the first to review this document.
Start a discussion about any aspect of this document.