Format: HTML | BibTeX | DC | EndNote | NLM | MARC | MARCXML
Published Article / ENY-ARTICLE-2012-314

Inefficacité des Paratonnerres à Avance d’Amorçage

Chrzan, K L (Wroclaw University of Technology) ; Teguar, M (Ecole Nationale Supérieure Polytechnique, Alger, Algérie)

2012-04-17

Abstract: Tests on three early streamer emission (ESE) terminals, manufactured by different firms, were carried out. The main measure criterion was the breakdown voltage of the air gap consisted of the high voltage electrode (rod or plate) and a grounded ESE terminal. Additionally, the time to breakdown was estimated from the oscillograms. The breakdown voltage was measured at standard switching impulses or under lightning impulses of both polarities or under AC voltage. The used distance ranged from 5 cm up to 4 m and voltage magnitude from 30 kV up to 2.5 MV. Except only one ESE terminal showing an advantage at an air gap of a few centimetres under AC voltage, these careful measurements show that the air gaps with ESE terminals have the same breakdown voltages as the air gaps with Franklin rods. Therefore, the large protection zone of ESE terminals, as claimed by their manufactures, is practically impossible.

Keyword(s): early streamer emission (ESE)terminals ; lightning protection
Note: Conference Nationale sur la Haute Tension, Sidi-Bel-Abbes, Algeria 2009, paper II-4


Fulltext : http://zet10.ipee.pwr.wroc.pl/record/401/files/

Cited by: try citation search for ENY-ARTICLE-2012-314

Record created 2012-04-25, last modified 2012-04-25

Similar records


 
People who viewed this page also viewed:
(558)  Power Swing Phenomena and its Detection and Prevention - Khan, U N et al - ENY-ARTICLE-2008-140
(526)  Impact of Distributed Generation on Electrical Power Network - Khan, U N - ENY-ARTICLE-2008-142
(523)  Zadania 1 Podstawy Elektrotechniki Automatyka i Robotyka - Hejke, I et al - ENY-TEACHING-2008-020
(518)  Elektrotechnika Teoretyczna. Analiza układów nieliniowych - Luczycki, A et al - ENY-BOOK-2008-002
(512)  Synthesis of Circuits - Leonowicz, Z - ENY-TEACHING-2008-025

 