Format: HTML | BibTeX | DC | EndNote | NLM | MARC | MARCXML
Preprint / http://www.sciencedirect.com/science/article/pii/S0378779613002198 ENY-PREPRINT-2013-013

Error Compensation in Distance Relays Caused by Wind Power Plants in the Power Grid

Trujillo, L (Universidad Autónoma de Nuevo León, Mexico) ; Conde, A (Universidad Autónoma de Nuevo León, Mexico) ; Leonowicz, Z (Wroclaw University of Technology, Poland)

2013-08-19

Abstract: This article presents the Prony method as a filtering technique for distance relays. First, the effect of non-filtered frequency components generated by Wind Power Plants in distance relays is evaluated in a simplified model of a doubly fed induction generator, resulting in an error of apparent impedance measurement. Then, the effects of non-filtered frequency components for typical distance relay are presented. The error in apparent impedance measurement is evaluated in reach and operation time of the relay; a distorted characteristic of the mho distance relay is shown in the impedance plane. Finally, Prony method as a filtering technique is implemented as a solution of the apparent impedance measurement error, and the simulated case and a real fault event are evaluated to validate the proposed distance relay algorithm. Thus the asynchronous frequency components of voltage and current signals are identified and filtered, as a result the performance of the distance relay is enhanced.

Keyword(s): wind power plant ; Prony method ; distance relay ; protective relays
Note: Preprint published in Electric Power Systems Research, Volume 106, January 2014, Pages 109–119 http://dx.doi.org/10.1016/j.epsr.2013.08.009


Fulltext : http://zet10.ipee.pwr.wroc.pl/record/442/files/

Cited by: try citation search for ENY-PREPRINT-2013-013; http://www.sciencedirect.com/science/article/pii/S0378779613002198

Rekord stworzony 2013-09-18, ostatnia modyfikacja 2013-09-19

Podobne rekordy


 
Osoby, które oglądały tę stronę, oglądały również:
(344)  Proceedings of the Int. Conference "7th EEEIC International Workshop on Environment and Electrical Engineering" - Schwarz, H et al - ENY-PREPRINT-2008-008
(340)  Zadania 1 Podstawy Elektrotechniki Automatyka i Robotyka - Hejke, I et al - ENY-TEACHING-2008-020
(332)  Evaluation of compensation devices of DC arc furnaces using advanced spectrum estimation methods - Bracale, A et al - ENY-ARTICLE-2008-011
(328)  Parametric methods for time-frequency analysis of electric signals - Leonowicz, Z - ENY-BOOK-2008-001
(328)  Impact of Distributed Generation on Electrical Power Network - Khan, U N - ENY-ARTICLE-2008-142

 
Oceń ten dokument:
Bądź pierwszy i oceń ten dokument.


Dyskusja nad tym dokumentem:
Rozpocznij dyskusję o tym dokumencie.