Format: HTML | BibTeX | DC | EndNote | NLM | MARC | MARCXML
Published Article / I07/91/P-443 ENY-ARTICLE-2008-057

Digital Line Differential Protection Using Symmetrical Components

Lobos, T (Wroclaw University of Technology)

1991-05-13

Abstract: A new method for digital line differential protection is presented. The protection compares the time function and the orthogonal function of the symmetrical positive- sequence component at the input and output of a transmission line. From these values the magnitude of the differential current is evaluated. The time function is calculated according to the SD4c algorithm and the orthogonal function according to the SD4s algorithm from four sampled triplets. The first results of the investigation are shown. By using this method, a phase-independent operating time of less than half a period can be obtained.

Keyword(s): digital line protection ; differential protection ; symmetrical components
Note: Elect. Power Syst. Res. 1991 Vol. 22 No. 2 pp. 85-89


Fulltext : http://zet10.ipee.pwr.wroc.pl/record/66/files/

Cited by: try citation search for ENY-ARTICLE-2008-057; I07/91/P-443

Record created 2008-03-14, last modified 2008-03-14

Similar records


 
People who viewed this page also viewed:
(869)  Impact of Distributed Generation on Electrical Power Network - Khan, U N - ENY-ARTICLE-2008-142
(866)  Zadania 1 Podstawy Elektrotechniki Automatyka i Robotyka - Hejke, I et al - ENY-TEACHING-2008-020
(866)  Elektrotechnika Teoretyczna. Analiza układów nieliniowych - Luczycki, A et al - ENY-BOOK-2008-002
(857)  Adaptacyjne sieci neuronowe w zastosowaniu do identyfikacji stanu układów elektrycznych - Kostyla, P - ENY-THESIS-2008-005
(844)  Proceedings of the Int. Conference "7th EEEIC International Workshop on Environment and Electrical Engineering" - Schwarz, H et al - ENY-PREPRINT-2008-008

 
Rate this document:
Be the first to review this document.


Discuss this document:
Start a discussion about any aspect of this document.