000000069 100__ $$aSaha, M$$uABB Automation Products AB
000000069 245__ $$aNew concept for fault location in series-compensated parallel lines
000000069 260__ $$c2000-12-20
000000069 300__ $$a6p
000000069 500__ $$a2000 IEEE Power Engineering Society Winter Meeting. Proceedings, Singapore, 23-27 January 2000 Piscataway, NJ : IEEE, cop. 2000. 6 s.
000000069 520__ $$aNew concept for fault location in series- compensated parallel lines is presented. The developed one-end fault location algorithm offsets the series compensation and the reactance effects as well as takes the countermeasure for the mutual coupling between parallel lines. Its distinctive feature relies in no requirement of the impedance data for the equivalent systems behind both the line terminals and for the possible extra link between the substations. Moreover, complete avoiding of pre-fault measurements is provided. The sample fault location cases for the fault data obtained from versatile ATP-EMTP simulations are included and discussed.
000000069 6531_ $$acapacitor compensated transmission lines
000000069 6531_ $$acoupled transmission lines
000000069 6531_ $$adigital recording
000000069 6531_ $$adistance algorithms
000000069 6531_ $$afault diagnosis
000000069 6531_ $$asimulation
000000069 700__ $$aWikstrom, K$$uABB Automation Products AB
000000069 700__ $$aIzykowski, J$$uWroclaw University of Technology
000000069 700__ $$aRosolowski, E$$uWroclaw University of Technology